Text Box: Open Manual Motor Starter
CMS Series 1HP-100HP

Jim D. Gray & Associates, Inc.

Supporting O.E.M.’s since 1977

972-699-9976

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Part No

Rated Current

Thermal Release Adj. Range

Magnetic Release Operating current

HP

UL Type E rated max short-circuit current

 

 

Standard

1 Phase 60Hz

3 phase 60Hz

 

 

115V

230V

200V

230V

460V

575V

240V

480V

600V

 

 

CMS-100S-17

17

11-17

221

1

3

3

5

10

15

100

50

10

 

 

CMS-100S-22

22

14-22

286

1½

3

5

7½

15

20

100

50

10

 

 

CMS-100S-26

26

18-26

338

2

3

7½

7½

15

20

100

50

10

 

 

CMS-100S-32

32

22-32

416

2

5

7½

10

20

30

100

50

10

 

 

CMS-100S-40

40

28-40

520

3

7½

10

10

30

30

100

50

10

 

 

CMS-100S-50

50

34-50

650

3

10

15

15

30

30

100

50

10

 

 

CMS-100S-63

63

45-63

819

5

10

20

20

40

60

100

40

10

 

 

CMS-100S-75

75

55-75

975

5

15

20

25

50

60

100

40

10

 

 

CMS-100S-90

90

70-90

1170

7½

20

25

30

60

75

100

40

10

 

 

CMS-100S-100

100

80-100

1300

10

20

30

30

75

100

100

40

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Part No

Rated Current

Thermal Release Adj. Range

Magnetic Release Operating current

HP

UL Type E rated max short-circuit current

 

 

High Break

1 Phase 60Hz

3 phase 60Hz

 

 

115V

230V

200V

230V

460V

575V

240V

480V

600V

 

 

CMS-100H-17

17

11-17

221

1

3

3

5

10

15

100

65

25

 

 

CMS-100H-22

22

14-22

286

1½

3

5

7½

15

20

100

65

20

 

 

CMS-100H-26

26

18-26

338

2

3

7½

7½

15