Jim D. Gray & Associates, Inc. |
|
Supporting O.E.M.’s since 1977 |
|
Electronic Overloads 0A to 80A |
|
ELECTRONIC OVERLOAD SELECTOR TABLE
Microprocessor based
Phase Protection Phase current unbalance: Trips within 5 seconds when the phase current unbalance exceeds 50% Phase Loss / Phase failure: Trips within 3 seconds when phase current is 70% unbalanced Phase reversal: Trips within 1 second with the event of reverse phase current or miswire Class 1-30: Infinitely selectable
Easy Installation Screw terminal and tunnel type terminal in single unit Installed with screws or 35mm din-rail
Fully Adjustable overload relay Six models cover up 1/4 to 50HP 1-5A range can be used with external CTs to cover applications over 80A Wide range current adjustment and Class 1-30 adjustment fits any application Built in stall protection provides maximum protection to the motor (trips at 170% of full load amps at 3 seconds)
Simplified operation & troubleshooting LED Indicates motor status and displays causes of faults including over / under current, failure by phase, & reversal
CONTACTORS & THERMAL OVERLOADS AVAILABLE
|
|
972-699-9976 |