UPS 16-240 UNINTERRUPTIBLE POWER SYSTEM

16KVA / 12.8KW OUTPUT 240VAC INPUT

Jim D. Gray & Associates, Inc.

Supporting O.E.M.’s since 1977

972-699-9976

HOME

ABOUT US

PRODUCT OVERVIEW

SERVICES

MANUFACTURERS

CONTACT US

NEWS

LINKS

GET A QUOTE

Input AC & Circuit  Breaker Requirements - standard connection

 

 

Input Voltage

240VAC @ 90A

Input voltage window

+15%, -20% of nominal VAC input @ full load/ +15%, -40% of nominal VAC input @ 50% load

Frequency

60Hz

Power Factor

0.98

AC Output ACV-Hardwire

120 / 208 / 220 / 230 / 240

Output Receptacles

Optional ( all types available )

Output Waveform

Computer grade sine wave output power with less than 5% total harmonic distortion @ rated kw load. Sine wave correcting regardless of voltage THD.

Regulation

+/-3%

Load Compatible

Guaranteed compatible with all loads including power factor corrected.

Overload

150% surge capability, overload alarm 101% load to 125% load for 10 min. before shutdown. Greater than 125% the system will shutdown in 5 seconds.

Output Protection

Output ferroresonant transformer provides inherent current limiting protection

Dimensions UPS

70.5" X 28"X 24.5"

Dimensions Battery Cabinet

56.5 X 18 X 24.5

Weight UPS ( lbs )

875

Weight Battery Cabinet ( lbs )

670 w / battery

Efficiency

91%

BTU's / Kw

2160 /.632

Noise Attenuation

120db common mode, 60db transverse (normal) mode

Isolation

Output is completely isolated from commercial power with less than 1 pf effective capacitive coupling primary to secondary. Secondary has neutral to ground bond, qualifying as a separately derived power source

Surge Protection

6000 volts are suppressed to safe levels per ANSI/IEEE C62.41-1997 category A & B waveforms

Operating Temperature

0° to 40°C (-4° to 104°F)

Relative Humidity

0 to 95% without condensation

High Altitude Operation

Max. altitude 10,000 ft - de-rate 1°C off max operating temp per 1000 ft. above sea level

Agency

UL 1778, cUL listed

User Interface

Keypad w/LCD display, RS232 serial communications, internal dial modem, dry contacts.

Events Monitored

Sags, surges, frequency shifts, voltage spikes, & glitches are recorded and time/date stamped

 

INVERTER

Nominal DC Voltage

96VDC

Charger Amps

8A

Runtime Full Load / Half Load

10 min. / 25 min.

Sound Level

53dbA

 

 

 

 

Top of page