Key Functions

Constant Current Charge  provides constant current for specified time

 

Dual Charge  two consecutive time periods with two separately specified constant current levels

 

Constant Potential Charge  - charges until battery voltage equals maximum voltage per cell X number of cells

 

Constant Current Discharge - discharge at a specified current for a preset period of time to measure capacity

 

Deep Discharge  can be performed by setting volts/cell below 1.0 with a low discharge current level

Self-Calibration

Self-Calibration for Current & Volts - allows technician to use a multimeter to calibrate the unit on the bench

Accessories

Battery Cable Assembly - connects battery being charged or analyzed with UNIVERSAL 60 with Elcon connector

 

Cell Scanning Probe Set - Test probes for manually checking cell voltages

 

SPECIFICATIONS

Mechanical

Dimensions: 18.5” X 21.5” X11”; Weight: 145 lbs; Case:  Steel

Electrical-Input

187-265VAC single phase 47-63Hz; Current requirements 25A max. ; Power switch: opens both sides of line

Electrical-Output

Constant Current: 1 to 60A;  Constant current discharge: 0.2 to 60A;  Constant potential charge: 75V max.

Electrical Displays

Current: 99.9 full scale, accuracy ±2% of full scale; Voltage 99.9 full scale, accuracy ±2% of full scale: Individual Cells: 19.99 full scale, accuracy ±2% of full scale

Environmental-Operating

Ambient Temperature 0°-50°C; Altitude: 0 to 8000 feet;  Designed to meet: EMI Mil-Std 460 & sand,dust Humidity of Mil-Std 810;  CE compliant versions available

Environmental-Storage

Ambient temperature: 40°C to 71°C; Altitude: 0-50,000 feet