Jim D. Gray & Associates, Inc.

Supporting O.E.M.’s since 1977

UL489 MOLDED CASE CIRCUIT BREAKERS

HVAC Rated 2-Pole

Fixed Thermal & Magnetic

25kA UL interrupt @ 480VAC

1-972-699-9976

HOME

ABOUT US

PRODUCT OVERVIEW

SERVICES

MANUFACTURERS

CONTACT US

NEWS

LINKS

GET A QUOTE

SEE UL489 CIRCUIT BREAKERS FOR OTHER RATINGS

 

SEE UL508 CIRCUIT BREAKERS FOR OTHER RATINGS

 

CRS SERIES

 

 

 

 

 

 

2-Pole

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   UL LISTED INTERRUPT RATINGS

 

 

 

 

 

240V AC

 50kA

 

 

 

 

 

 

480V AC

 25kA

 

 

 

 

 

 

600V AC

 14kA (no rating for 100AF)

 

 

 

 

 

 

Model No

LG Industrial Part No.

FRAME SIZE

AMP RATING  (In)

MAGNETIC TRIP SETTING

 

 

 

 

 

 

CRS102U-15

ABS102U-15A

100AF

15

500A

 

 

 

 

 

 

CRS102U-20

ABS102U-20A

100AF

20

500A

 

 

 

 

 

 

CRS102U-30

ABS102U-30A

100AF

30

500A

 

 

 

 

 

 

CRS102U-40

ABS102U-40A

100AF

40

500A

 

 

 

 

 

 

CRS102U-50

ABS102U-50A

100AF

50

500A

 

 

 

 

 

 

CRS102U-60

ABS102U-60A

100AF

60

600A

 

 

 

 

 

 

CRS102U-80

ABS102U-80A

100AF

80

800A

 

 

 

 

 

 

CRS102U-100

ABS102U-100A

100AF

100

1000A

 

 

 

 

 

 

CRS202U-125

ABS202U-125A

225AF

125

5,6,7,8,9,10 X In (adjustable)

 

 

 

 

 

 

CRS202U-150

ABS202U-150A

225AF

150

5,6,7,8,9,10 X In (adjustable)

 

 

 

 

 

 

CRS202U-175

ABS202U-175A

225AF

175

5,6,7,8,9,10 X In (adjustable)

 

 

 

 

 

 

CRS202U-200

ABS202U-200A

225AF

200

5,6,7,8,9,10 X In (adjustable)

 

 

 

 

 

 

CRS202U-225

ABS202U-225A

225AF

225

5,6,7,8,9,10 X In (adjustable)

 

 

 

 

 

 

CRS402U-250

ABS402U-250A

400AF

250

2500A

 

 

 

 

 

 

CRS402U-300

ABS402U-300A

400AF

300

3000A

 

 

 

 

 

 

CRS402U-350

ABS402U-350A

400AF

350

3500A

 

 

 

 

 

 

CRS402U-400

ABS402U-400A

400AF

400

4000A

 

 

 

 

 

 

CRS602U-500

ABS602U-500A

600AF

500

5000A

 

 

 

 

 

 

CRS602U-600

ABS602U-600A

600AF

600

6000A

 

 

 

 

 

 

UL magnetic trip setting tolerances are -20% and +30% from the nominal values shown

 

 

 

 

100AF, 400AF & 600AF units have fixed thermal and magnetic over current device     

 

 

 

 

 

 

225AF units have fixed thermal & adjustable magnetic over current device

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ACCESSORIES

 

 

 

 

 

 

Model No.

Description

 

 

 

 

 

 

AX-225

Aux. contact for 100AF & 225AF

 

 

 

 

 

 

AX-600

Aux. contact for 400AF & 600AF

 

 

 

 

 

 

AL-225

Alarm switch for 100AF & 225AF

 

 

 

 

 

 

AL-600

Alarm switch for 400AF & 600AF

 

 

 

 

 

 

SHT-225

Shunt trip for 100AF & 225AF

 

 

 

 

 

 

SHT-600

Shunt trip for 400AF & 600AF

 

 

 

 

 

 

UVT-225

Under voltage trip for 100AF & 225AF

 

 

 

 

 

 

UVT-600

Under voltage trip for 400AF & 600AF

 

 

 

 

 

 

CI-23S

Mechanical interlock for 100AF & 225AF

 

 

 

 

 

 

CI-43S

Mechanical interlock for 400AF

 

 

 

 

 

 

CI-63S

Mechanical interlock for 600AF

 

 

 

 

 

 

C-225S

Handles/operators (NEMA 1) for 100AF & 225AF

 

 

 

 

 

 

C-400S

Handles/operators (NEMA 1) for 400AF

 

 

 

 

 

 

C-600S

Handles/operators (NEMA 1) for 600AF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Contact Ratings for AX & AL auxiliary contacts

 

 

 

AC

DC

 

 

 

 

Max switching current

 

 

Max switching current

 

 

 

Operational voltage

Operational voltage

 

 

 

 

 

Res. Load

Ind. Load

 

Res. Load

Ind. Load

 

 

 

125

 

5

3

30

 

4

3

 

 

 

230

 

3

2

125

 

0.4

0.4

 

 

 

--

 

--

--

250

 

0.2

0.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Ratings for Under Voltage Trip  - UVT (All frames)

 

 

 

AC/DC Common

24/48/100~110/200~220V

 

 

 

DC

380~440V, 440~480V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Ratings for Shunt Trip - SHT

 

 

 

 

 

 

100AF        225AF

400AF          600AF

 

 

AC/DC Common

 

 

24~48V

 

 

12/24/48/60/250V

AC200~240/DC200~220V

 

 

 

 

AC100~125/DC100~110V

 

 

 AC

 100~125/200~240V

 

 

 

 

 

 380~450/440~480V

380-460/480-550V

 

 

 500~550V

 

 

 

 

 

 DC

 

 

 

 

 

 

 100~110/125/200~220

---

 

 

 240/250

 

 

 

 

 

Operational voltage

75-110% of rated volts

 

75-110% of rated volts