Jim D. Gray & Associates, Inc. |
|
Supporting O.E.M.’s since 1977 |
|
UL489 MOLDED CASE CIRCUIT BREAKERS HVAC Rated 3-POLE Fixed Thermal & Magnetic 50kA UL interrupt @ 480VAC |
|
972-699-9976 |
|
|
CRL SERIES |
|
|
|
|
|
||||
|
|
3-Pole |
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
UL LISTED INTERRUPT RATINGS |
|
|
|
|
|||||
|
|
240V AC |
100kA |
|
|
|
|
|
|||
|
|
480V AC |
50kA |
|
|
|
|
|
|||
|
|
600V AC |
18kA (no rating for 100AF) |
|
|
|
|
|
|||
|
|
Model No |
LG industrial Part No. |
FRAME SIZE |
AMP RATING (In) |
MAGNETIC TRIP SETTING |
|
|
|
|
|
|
|
CRL103U-15 |
ABL103U-15A |
100AF |
15 |
500A |
|
|
|
|
|
|
|
CRL103U-20 |
ABL103U-20A |
100AF |
20 |
500A |
|
|
|
|
|
|
|
CRL103U-30 |
ABL103U-30A |
100AF |
30 |
500A |
|
|
|
|
|
|
|
CRL103U-40 |
ABL103U-40A |
100AF |
40 |
500A |
|
|
|
|
|
|
|
CRL103U-50 |
ABL103U-50A |
100AF |
50 |
500A |
|
|
|
|
|
|
|
CRL103U-60 |
ABL103U-60A |
100AF |
60 |
600A |
|
|
|
|
|
|
|
CRL103U-80 |
ABL103U-80A |
100AF |
80 |
800A |
|
|
|
|
|
|
|
CRL103U-100 |
ABL103U-100A |
100AF |
100 |
1000A |
|
|
|
|
|
|
|
CRL203U-125 |
ABL203U-125A |
225AF |
125 |
5,6,7,8,9,10 X In (adjustable) |
|
|
|
|
|
|
|
CRL203U-150 |
ABL203U-150A |
225AF |
150 |
5,6,7,8,9,10 X In (adjustable) |
|
|
|
|
|
|
|
CRL203U-175 |
ABL203U-175A |
225AF |
175 |
5,6,7,8,9,10 X In (adjustable) |
|
|
|
|
|
|
|
CRL203U-200 |
ABL203U-200A |
225AF |
200 |
5,6,7,8,9,10 X In (adjustable) |
|
|
|
|
|
|
|
CRL203U-225 |
ABL203U-225A |
225AF |
225 |
5,6,7,8,9,10 X In (adjustable) |
|
|
|
|
|
|
|
CRL403U-250 |
ABL403U-250A |
400AF |
250 |
2500A |
|
|
|
|
|
|
|
CRL403U-300 |
ABL403U-300A |
400AF |
300 |
3000A |
|
|
|
|
|
|
|
CRL403U-350 |
ABL403U-350A |
400AF |
350 |
3500A |
|
|
|
|
|
|
|
CRL403U-400 |
ABL403U-400A |
400AF |
400 |
4000A |
|
|
|
|
|
|
|
CRL603U-500 |
ABL603U-500A |
600AF |
500 |
5000A |
|
|
|
|
|
|
|
CRL603U-600 |
ABL603U-600A |
600AF |
600 |
6000A |
|
|
|
|
|
|
|
UL magnetic trip setting tolerances are -20% and +30% from the nominal values shown |
|
|
|
||||||
|
|
100AF, 400AF & 600AF units have fixed thermal and magnetic over current device |
|
|
|
|
|
||||
|
|
225AF units have fixed thermal & adjustable magnetic over current device |
|||||||||