Jim D. Gray & Associates, Inc. |
|
Supporting O.E.M.’s since 1977 |
|
972-699-9976 |
|
Input Voltage 3-phase 60Hz |
208 Wye |
|
Input voltage window |
+15%, -20% of nominal VAC input @ full load / +15%, -40% of nominal VAC @ 50% load |
|
AC Output |
Any single phase output available |
|
Regulation |
±3% |
|
Load Compatibility |
Guaranteed compatible with all loads |
|
Overload |
Inherent overload protection - immediate recovery when overload is removed |
|
Noise Attenuation |
120db common mode 60db transverse (normal) mode |
|
Isolation |
Complete isolation from utility power with less than 2 pf effective capacitive coupling primary to secondary |
|
Surge Protection |
6000 volts are suppressed to safe levels per ANSI / IEEE C62.41-1997 category A & B waveforms |
|
Operating Temperature |
0°C to 50°C (-4°F to 104°F) |
|
Relative Humidity |
0 to 94% |
|
High Altitude Operation |
Max. altitude 10,000 ft. derate 1°C off max operating temp per 1000ft above sea level |
|
Heat Loss (BTU / Hour) |
|
|
Efficiency |
85% |
|
Dimensions |
17"D X 17"W X 22"H |
|
U S Patent No. |
6,166,531 |