Jim D. Gray & Associates, Inc. - Distributing |
|
CAGE NO. 4XGF3 DUNS 178043733 |
|
972-699-9976 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Variable Torque |
Constant Torque |
|
|
|
|
|
|
||||||
|
|
Part No. |
|
Motor Rating |
Motor Rating |
Output Ratings |
Input Ratings |
|
|
|
|
||||||
|
|
|
|
HP |
kW |
A |
HP |
kW |
A |
Voltage |
Frequency |
Voltage |
Frequency |
Dimensions |
Weight |
|
|
|
|
CI-007-P2 |
|
7.5 |
5.5 |
24 |
5 |
3.7 |
17 |
3-Ø, 200-230V |
0~120 Hz* |
3-Ø, 200-230V (+10%, -15%) |
50-60 Hz (±5%) |
11.19" X 5.91" x 6.17" |
10.8 lbs |
|
|
|
|
CI-010-P2 |
|
10 |
7.5 |
32 |
7.5 |
5.5 |
23 |
3-Ø, 200-230V |
0~120 Hz* |
3-Ø, 200-230V (+10%, -15%) |
50-60 Hz (±5%) |
11.19" X 7.88" x 7.17" |
13.2 lbs |
|
|
|
|
CI-015-P2 |
|
15 |
11 |
46 |
10 |
7.5 |
33 |
3-Ø, 200-230V |
0~120 Hz* |
3-Ø, 200-230V (+10%, -15%) |
50-60 Hz (±5%) |
11.19" X 7.88" x 7.17" |
13.2 lbs |
|
|
|
|
CI-020-P2 |
|
20 |
15 |
60 |
15 |
11 |
44 |
3-Ø, 200-230V |
0~120 Hz* |
3-Ø, 200-230V (+10%, -15%) |
50-60 Hz (±5%) |
15.17" X 9.85" x 7.92" |
28.7 lbs |
|
|
|
|
CI-025-P2 |
|
25 |
18.5 |
74 |
20 |
15 |
54 |
3-Ø, 200-230V |
0~120 Hz* |
3-Ø, 200-230V (+10%, -15%) |
50-60 Hz (±5%) |
15.17" X 9.85" x 7.92" |
29.8 lbs |
|
|
|
|
CI-030-P2 |
|
30 |
22 |
88 |
25 |
18.5 |
68 |
3-Ø, 200-230V |
0~120 Hz* |
3-Ø, 200-230V (+10%, -15%) |
50-60 Hz (±5%) |
18.12" X 11.98" X 9.22" |
44.1 lbs |
|
|
|
|
CI-040-P2 |
|
40 |
30 |
115 |
30 |
22 |
84 |
3-Ø, 200-230V |
0~120 Hz* |
3-Ø, 200-230V (+10%, -15%) |
50-60 Hz (±5%) |
18.12" X 11.98" X 9.22" |
44.1 lbs |
|
|
|
|
|
|
|
|
|
|||||||||||
|
|
OPTIONS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CI-485-COM |
|
RS485 communication card |
|
|
|
|
|
|
|
|
|
|
|||
|
|
CI-MB-COM |
|
ModBus-RTU communication card STANDARD |
|
|
|
|
|
|
|
|
|||||
|
|
CI-DN-COM |
|
DeviceNet communication card |
|
|
|
|
|
|
|
|
|
|
|||
|
|
CI-N2-COM |
|
N2 communication card |
|
|
|
|
|
|
|
|
|
|
|
||
|
|
CI-PB-COM |
|
ProfiBus communication card |
|
|
|
|
|
|
|
|
|
|
|||
|
|
CI-BN-COM |
|
BACnet communication card |
|
|
|
|
|
|
|
|
|
|
|||
|
|
CI-LW-COM |
|
LonWorks communication card |
|
|
|
|
|
|
|
|
|
|
|||
|
|
CI-LCD-EXT2M |
|
2 meter cable (remote mounting cable between inverter and keypad fixture |
|
|
|
|
|
|
|||||||
|
|
CI-LCD-EXT3M |
|
3 meter cable (remote mounting cable between inverter and keypad fixture |
|
|
|
|
|
|
|||||||
|
|
CI-LCD-EXT5M |
|
5 meter cable (remote mounting cable between inverter and keypad fixture |
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Control Method |
|
|
|
V/F Control Sensorless vector control |
|
|
|
|
|
|||
|
|
|
|
|
Freq. setting resolution |
|
|
Digital reference: 0.01Hz (below 99Hz) & 0.1Hz (100Hz and over) Analog reference 0.03hz @ 60 Hz |
|
|
|||||||
|
|
|
|
|
Freq. setting accuracy |
|
|
Digital: 0.01% of maximum output frequency Analog: .1% of maximum output frequency |
|
|
|
||||||
|
|
|
|
|
V/F Ratio |
|
|
|
|
Linear Square User V/F |
|
|
|
|
|
||
|
|
|
|
|
Overload Capacity |
|
|
1 minute @ 110% 30 seconds @ 150% (with inverse characteristic proportional to time) |
|
|
|
||||||
|
|
|
|
|
Torque boost |
|
|
|
Auto Manual (0~15%) |
|
|
|
|
|
|||
|
|
|
|
|
Multi-function input terminals |
|
Total 8 inputs (programmable) |
|
|
|
|
|
|||||
|
|
|
|
|
Analog output |
|
|
|
0~10V linear |
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Input Signal |
Operator control |
|
|
|
32 Character LCD keypad 4 digits LED keypad Terminals ModBus-RTU communication |
|
|
|
|||||||
|
|
|
|
|
|
|
|
Optional ModBus-RTU ProfiBus-DP RS485 DeviceNet F-Net |
|
|
|
|
|||||
|
|
Frequency setting |
|
|
|
Analog: 0~10V, 4-20mA, additional port for Sub-board (0-10V) Digital Keypad Communication |
|
|
|||||||||
|
|
Start signal |
|
|
|
Forward Reverse |
|
|
|
|
|
||||||
|
|
Multi-step operation |
|
|
Setting up to 8 speeds using multi-function terminals |
|
|
|
|
||||||||
|
|
Multi-step accel/decel time |
|
0.1~6000 seconds. Maximum 8 pre-defined steps using multi-funtion terminals |
|
|
|
||||||||||
|
|
Operation functions |
|
|
DC braking Frequency Limit Frequency Jump Second motor function Slip compensation |
|
|
||||||||||
|
|
|
|
|
|
|
|
Reverse rotation prevention Auto Restart Inverter bypass Auto tuning PID control |
|
|
|
||||||
|
|
Emergency stop |
|
|
|
Interrupting output from inverter |
|
|
|
|
|
||||||
|
|
Auto Operation |
|
|
|
Operates from internal sequence by setting multi-function terminal (5 way X 8 step) |
|
|
|
||||||||
|
|
Jog |
|
|
|
|
|
Jog operation |
|
|
|
|
|
||||
|
|
Fault Reset |
|
|
|
Resets fault signal when protective function is active |
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Output signal |
Operational Status |
|
|
Frequency detection Overload alarm Stall Overvoltage Undervoltage Inverter overheat Run |
|
|
|||||||||
|
|
|
|
|
|
|
|
Stop Constant speed Speed search Fault output (relay and open collector output) Inverter bypass |
|
|
|||||||
|
|
|
|
|
|
|
|
Auto operation step Auto operation sequence |
|
|
|
|
|||||
|
|
Indicator |
|
|
|
|
Output frequency Output current Output voltage DC voltage Output torque (output voltage 0-10V) |
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Protective Functions |
Trip |
|
|
|
|
|
Overvoltage Undervoltage Overcurrent Inverter overheat Motor overheat I/O phase loss |
|
|
||||||
|
|
|
|
|
|
|
|
I/O miss wiring Fuse open Ground fault External fault 1,2 Option fault Overload |
|
|
|
||||||
|
|
|
|
|
|
|
|
Speed command loss Hardware fault Communication error |
|
|
|
|
|||||
|
|
Alarm |
|
|
|
|
Stall Overload Temperature sensor fault |
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Operating environment |
Ambient Temp |
|
|
|
-10°~40°C |
|
|
|
|
|
|
||||
|
|
Storage Temp |
|
|
|
-20°~65°C |
|
|
|
|
|
|
|||||
|
|
Humidity |
|
|
|
|
90% RH max(non condensing) |
|
|
|
|
|
|||||
|
|
Altitude & vibration |
|
|
1000m max, 5.9m/sec²(0.6g)max. |
|
|
|
|
|
|||||||
|
|
Application site |
|
|
|
No corrosive gas, flammable gas, oil mist or dust |
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
||||||||||