Jim D. Gray & Associates, Inc. |
|
Supporting O.E.M.’s since 1977 |
|
PPC 8-208 POWER CONDITIONER VOLTAGE REGULATOR 8KVA / 6.4KW OUTPUT 208VAC INPUT |
|
972-699-9976 |
|
Input AC & Circuit breaker requirements - standard connection |
|
|
|
|
|
Input Voltage |
208VAC 60A |
|
Input voltage window |
+15%, -30% of nominal VAC input @ full load/ +15%, -40% of nominal VAC input @ 50% load |
|
Frequency |
60Hz |
|
Input THD |
5% or less |
|
AC Output Voltage |
120 / 208 / 240 |
|
Output Receptacles |
Optional |
|
Output Waveform |
Computer grade sine wave output power into resistive load |
|
Regulation |
+/-1% |
|
Load Compatible |
Guaranteed compatible with all loads |
|
Overload |
150% surge capability, overload alarm 101% load to 125% load for 10 min. before shutdown. Greater than 125% the system will shutdown in 5 seconds. |
|
Dimensions |
19.25" X 17.5" X 21.5" |
|
Weight |
390 lbs |
|
Efficiency |
93% |
|
BTU's/Kw |
1645 /.482 |
|
Noise Attenuation |
120db common mode, 60db transverse (normal) mode |
|
Isolation |
Output is completely isolated from commercial power with less than 2 pf effective capacitive coupling primary to secondary. Secondary has neutral to ground bond, qualifying as a separately derived power source |
|
Surge Protection |
6000 volts are suppressed to safe levels per ANSI/IEEE C62.41-1997 category A & B waveforms |
|
Operating Temperature |
0° to 40°C (-4° to 104°F) |
|
Relative Humidity |
0 to 95% without condensation |
|
High Altitude Operation |
Max. altitude 10,000 ft - derate 1°C off max operating temp per 1000 ft. above sea level |
|
Agency |
UL 1778, cUL listed |
|
User Interface |
Keypad w/LCD display, RS232 serial communications, dial in modem |
|
|
|
|
|
|
|
|
|