Jim D. Gray & Associates, Inc.

Supporting O.E.M.’s since 1977

PPC 4-120 POWER CONDITIONER VOLTAGE REGULATOR

4KVA / 3.2KW OUTPUT 120VAC INPUT

972-699-9976

HOME

ABOUT US

PRODUCT OVERVIEW

SERVICES

MANUFACTURERS

CONTACT US

NEWS

LINKS

GET A QUOTE

Input AC & Circuit breaker requirements - standard connection

 

 

Input Voltage

120VAC   50A

Input voltage window

+15%, -30% of nominal VAC input @ full load/ +15%, -40% of nominal VAC input @ 50% load

Frequency

60Hz

Input THD

5% or less

AC Output Voltage

120 / 208 / 240

Output Receptacles

Optional

Output Waveform

Computer grade sine wave output power into resistive load

Regulation

+/-1%

Load Compatible

Guaranteed compatible with all loads

Overload

150% surge capability, overload alarm 101% load to 125% load for 10 min. before shutdown.  Greater than 125% the system will shutdown in 5 seconds.

Dimensions

17.5" X 17.5" X 21.5"

Weight

220 lbs

Efficiency

91%

BTU's/Kw

1080 /.316

Noise Attenuation

120db common mode,  60db transverse (normal) mode

Isolation

Output is completely isolated from commercial power with less than 2 pf effective capacitive coupling primary to secondary. Secondary has neutral to ground bond, qualifying as a separately derived power source

Surge Protection

6000 volts are suppressed to safe levels per ANSI/IEEE C62.41-1997 category A & B waveforms

Operating Temperature

0° to 40°C (-4° to 104°F)

Relative Humidity

0 to 95% without condensation

High Altitude Operation

Max. altitude 10,000 ft - derate 1°C off max operating temp per 1000 ft. above sea level

Agency

UL 1778, cUL listed

User Interface

Keypad w/LCD display, RS232 serial communications, dial in modem