Jim D. Gray & Associates, Inc. |
|
Supporting O.E.M.’s since 1977 |
|
DIGITAL MOTOR PROTECTION RELAY 0.5A-60A Motor protection against over current, phase failure, asymmetry, stall, phase reversal & under current. |
|
972-699-9976 |
|
|
|
|
|
Current Setting Range |
Motor Capacity |
|
|
|
|
|
|
|
|
|
220-240V |
380-440V |
Wiring |
|
|
|
|
|
CDP06-S |
|
|
0.5-6 |
0.09-0.75 |
0.12-1.5 |
Screw |
|
|
|
|
CDP60-S |
|
|
5-60 |
1.1-11 |
2.2-22 |
Screw |
|
|
|
|
CDP06-T |
|
|
0.5-6 |
0.9-0.75 |
0.12-1.5 |
Tunnel |
|
|
|
|
CDP60-T |
|
|
5-60 |
1.1-11 |
2.2-22 |
Tunnel |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Panel mount |
|
|
Unit or extension |
|
|
|
|
|
|
|
Operation time |
|
|
Select: reverse time characteristics or definite time characteristics |
|
||||
|
|
Alarm |
|
|
Variable (60-110% of the setting current) |
|
|
|
||
|
|
Time setting range (sec) |
Definite time |
Delay in starting |
0-60 sec. |
|
|
|
|
|
|
|
Delay in operating |
0-30 sec. |
|
|
|
|
|
||
|
|
|
Inverse Time |
0-60 sec. |
|
|
|
|
|
|
|
|
|
Reset |
Manual reset |
|
|
|
|
||
|
|
Tolerance |
|
Current |
±5% |
|
|
|
|
|
|
|
|
Time |
±5% (or ±5 sec.) |
|
|
|
|
||
|
|
Operating power |
|
Voltage |
AC 190-250V |
|
|
|
|
|
|
|
|
Frequency |
60Hz (50Hz) |
|
|
|
|
||
|
|
Aux. contact |
OL |
2-SPST |
3A/250VAC resistive load |
|
|
|
|
|
|
|
AL |
SPST |
3A/250VAC resistive load |
|
|
|
|
||
|
|
Insulation resistance |
|
|
Over DC 500V 100Ω |
|
|
|
|
|
|
|
Surge impulse (IEC 1000-4-5) |
|
1.2 X 50 μs 6kV (apply standard wave form) |
|
|
|
|
||
|
|
Fast transient burst (IEC 1000-4-4) |
|
2.5 kV/5 min. |
|
|
|
|
||
|
|
Environment |
|
Oper. Temp. |
-25-70°C |
|
|
|
|
|
|
|
|
Storage Temp. |
-30- 80°C |
|
|
|
|
|
|
|
|
|
Humidity |
30-90% RH (no freezing) |
|
|
|
|
||
|
|
Display |
|
7-segment |
3-phase current, cause of a fault |
|
|
|
||
|
|
|
Bar-graph |
60-110% of real load current |
|
|
|
|||
|
|
Mounting Type |
|
|
35mm din-rail/panel |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Ground fault detection & extension cables |
|
|||||||
|
|
ZCT D30 |
|
ZCT for ground fault detection - 30mm opening |
|
|
|
|||
|
|
ZCT D50 |
|
ZCT for ground fault detection - 50mm opening |
|
|
|
|||
|
|
ZCT D65 |
|
ZCT for ground fault detection - 65mm opening |
|
|
|
|||
|
|
ZCT D80 |
|
ZCT for ground fault detection - 80mm opening |
|
|
|
|||
|
|
CDP-Cable 1M |
|
Extension cable for remote mounting of display - 1 meter |
|
|
||||
|
|
CDP-Cable 2M |
|
Extension cable for remote mounting of display - 2 meter |
|
|
||||
|
|
CDP-Cable 3M |
|
Extension cable for remote mounting of display - 3 meter |
|
|
||||
|
|
|
|
|
|
|
|
|||